Specifications 1Set 36kW 47U Rack Space I for Air-cooling Servers
Payment Method
USDBTCETCUSDC(ERC20)USDT(ERC20/TRC20)
Specifications
| Product Glance | Value |
| Model | DCRACK |
| Version | V1 |
| Capacity | 47U |
| Maximum load,kW | 36 |
| PUE@25℃ ambient, 25℃ air supply(1-1) | 1.17 |
| Supply air temperature for classic server, ℃ | 18~27℃ |
| Detailed Characteristics | Value |
| Part 1: Server Cabinet | Value |
| Hardware Configuration | |
| Size (Length*Width*Height), mm (without package) | 1,600*1,200*2,350 |
| Size (Length*Width*Height), mm (with package) | 1,720*1,300*2,400 |
| Net weight, kg (without package) | 668 |
| Gross weight, kg (with package) | 686 |
| Network connection mode | RJ45 Ethernet 10/100M |
| Power Supply | |
| Power supply AC Input voltage, Volt(2-1) | 380~415 AC |
| Power supply AC Input Frequency Range, Hz | 50~60 |
| Maximum Power supply AC Input current, Amp(2-2) | 63 |
| Fan | |
| Rated power, W | 2,500 |
| Noise, dBA@1m | 85 |
| Size (Length*Width* Thickness), mm | 378*378*375 |
| Number of fans | 3 |
| Part 2: External Cooler | Value |
| Hardware Configuration | |
| Size (Length*Width*Height), mm (without package) | 1,896*1,026*2,180 |
| Size (Length*Width*Height), mm (with package) | 2,000*1,130*2,360 |
| Net weight, kg (without package) | 396 |
| Gross weight, kg (with package) | 414 |
| Power Supply | |
| Power supply AC Input voltage, Volt(2-1) | 380~415V AC |
| Power supply AC Input Frequency Range, Hz | 50~60 |
| Maximum Power supply AC Input current, Amp(2-2) | 63 |
| Heat pump | |
| Rated power, kW | 8.5 |
| COP (typical) | 4.75 |
| Refrigerant | R410A |
| Fan | |
| Rated power, kW | 1.85 |
| Noise, dBA@1m | 82 |
| Size (Length*Width* Thickness), mm | 805*805*211 |
| Number of fans | 2 |
| Refrigerant pump | |
| Rated power, W | 550 |
| Flow rate, m3/h | 1 |
| Pump head, m | 48 |
| Size (Length*Width* Height), mm | 420*152*202 |
| Environment requirements | Value |
| Ambient temperature, °C | -20~45℃ |
| Installation distance (max), m(2-3) | 50 |
| Storage temperature, °C | -20~70 |
| Operation humidity(non-condensing), RH | 10~90% |
Notes:
(1-1) The typical PUE is tested at 25℃ ambient and 25 ℃ air supply, without water curtain.
(2-1) Caution: Wrong input voltage may cause server damaged.
(2-2) Three-phase AC input.
(2-3) The distance between server cabinet and external cooler.
Contact: Amanda
Phone: 86-755-83240143
E-mail: thebestasicminers@gmail.com
Whatsapp:+8613424370509
Add: 1nd Floor,No.51 Building,Dongwu Industrial Park,Donghuan 1st Road,Pingshan New District, Shenzhen